Hydrogen Delivery Truck Roll Over Accident
When Incident Was Discovered
Severity
Incident
Was Hydrogen Released?
Yes
Was There Ignition?
No
Equipment
Damage and Injuries
Probable Cause
Contributing Factors
Describe the incident, including corrective steps taken and their result.
Incident Synopsis
A H2 delivery truck accident occurred on a highway. The truck was pulling a trailer containing gaseous H2. Upon entering a sharp curve, the truck and trailer started to weave and pushed to the side of the road. The truck and trailer rolled about 40 feet downhill; the trailer rolled over 1 1/2 times and the tractor once, ending in the upright position with the driver still in his seat. The truck was completely totaled, but little damage was incurred by the trailer. The trailer shell was satisfactory with normal venting through the stack. The rear cabinet doors were warped shut.
Cause
- The accident occurred on a bad road, which was steep with many sharp curves. The driver was going too fast for the road conditions and the type of trailer being pulled.
- The truck driver was also used to transporting a liquid H2 trailer, which was smaller and had different weight and handling characteristics.