High-Temperature Heat Exchanger Flange Leak Leads to Hydrogen Fire
Incident Date
When Incident Was Discovered
Severity
Incident
Was Hydrogen Released?
Yes
Was There Ignition?
Yes
Setting
Equipment
Damage and Injuries
Probable Cause
Describe the incident, including corrective steps taken and their result.
Overview
During start-up operation of a high-temperature, high-pressure plant using hydrogen, hydrogen gas leaked from the flange of a heat exchanger and a fire occurred. The leakage occurred for two reasons:
- Insufficient tightening torque control was carried out during hot-bolting and an unbalanced force was generated across the bolts.
- A temperature rise was induced across the heat exchanger as a result of a revamping activity, during a turnaround shutdown.
Background
Hot-bolting: In equipment and piping that operate at high temperatures, as the temperatures rise, the tightening force decreases, thus re-tightening of bolts is necessary. This work is called hot-bolting. The design conditions of the evaporator where the fire occurred were 2.4 MPaG, and 500 °C at the shell side, and 2.8 MpaG, 300 °C at the tube side, and it required hot-bolting.
Sequence of Events
- A turnaround shutdown of the benzene manufacturing plant was carried out in June.
- A gas-tightness test with real gas (hydrogen and another gas) was completed in September, and normal plant operation was initiated.
- During warm-up operation of the benzene manufacturing plant, which uses hydrogen at high temperatures and pressures; hydrogen gas leaked through a heat exchanger flange, and a fire occurred. At the plant, benzene was produced by a dealkylation reaction using toluene and C9 aromatic hydrocarbon as raw material.
Causes
- There was unbalanced tightening torque among bolts of the flange.
- The shell-side inlet temperature rose from the previous 400 °C to 420 °C as a result of an energy-saving revamping.
- A decrease in tightening torque was locally generated by a difference in thermal expansion between bolts made of stainless steel and the flange made of carbon steel. Thermal expansion of stainless steel is greater than that of carbon steel.
- The ignition source was considered to be static electricity generated at leakage.
- Quantitative control of tightening torque of the bolt was insufficient, and there was a local shortage of initial tightening torque.
- It is speculated that there might be an insufficient work standard for hot-bolting or imperfect execution of hot-bolting.
- The temperature rose as a result of an energy-saving revamping, and the effects might have been overlooked.