Battery Room Explosion
A hydrogen explosion occurred in an Uninterruptible Power Source (UPS) battery room. The explosion blew a 400 ft2 hole in the roof, collapsed numerous walls and ceilings throughout the building, and significantly damaged a large portion of the 50,000 ft2 building. Fortunately, the computer/data center was vacant at the time and there were no injuries.
The facility was formerly a large computer/data center with a battery room and emergency generators. The company vacated the building and moved out the computer equipment; however the battery back-up system was left behind. The ventilation for the battery room appeared to be tied into a hydrogen monitoring system. The hydrogen sensor was in alarm upon emergency responders arriving at the scene (post-explosion). 911 callers reporting the explosion also reported hearing an alarm for 3 days prior to the explosion. This appears to have been a local alarm, as it was not relayed at any time to the local fire department. Given how slowly batteries generate H2 (1.3x10-7m/s per amp-cell), it appears as though batteries were charging for a long period of time with no ventilation. Apparently the detector was alarming, and hydrogen continued to build up until it found an ignition source. Due to the damage and actions of emergency responders shutting off all circuit breakers, etc., it could not be verified whether the ventilation system failed, or was previously turned off when the building was vacated. Onsite personnel assumed that the ignition occurred at or near a grounding strap on the battery racks, but in a room full of batteries and electrical equipment, ignition sources are plentiful.
