- Home
-
Resources
- Center for Hydrogen Safety
- Hydrogen Fuel Cell Codes and Standards
- Paper & References
- Web-based Toolkits
- Workforce Development

- Contact
- About H2Tools
A leak occurred near the bottom of a stationary liquid hydrogen tank with a capacity of a 6,000-gallon. The leak was localised on a valve and was visible due to the air condensation forming white…
The safety disc failed during unloading from a liquid hydrogen tanker. The release of cryogenic hydrogen resulted in fracturing a section of the vent pipe. [Ordin, NASA (1974)]
A liquid hydrogen tanker was traveling west bound on a highway, when adverse weather conditions (snow and wind) caused a brief "whiteout". To avoid a group of vehicles stopped in front…
A liquid hydrogen tank tanker detached from the tractor due to equipment failure. The liquid hydrogen was tansferred to another tanker. During this operation a release of 58,000 cu ft occurred.…
According to local news, a "hydrogen tanker truck hauling was on fire" at a travel centre on a highway. The videos show, however, simply a flame from what probably is the pressure relief…
Excessive delay in trip resulted in over-pressure on the liquid hydrogen tank, requiring manual venting. This resulted in releasing of 2750 cu ft of hydrogen [Zalosh and Short, 1978]
The drivers failed to lower the internal pressure of a liquid hydrogen tanker before leaving plant. Therefore they had to stop en route and vent 4000 scf of hydrogen. [Zalosh and Short, 1978]
A liquid hydrogen tanker was returning empty to the base, when a pressure build-up forced the drivers to perform a manual venting. [Zalosh and Short, 1978]
Before loading it with liquid hydrogen, the cyrogenic tank had been purged with nitrogen for maintenance work. After the loading, the drivers failed to stabilise the internal pressure of the tank,…
The pressure building valve opened due to vibration from the road, causing the build-up of the internal pressure. The drivers performed a hydrogen venting and re-sealed the valve. [Zalosh and…
While returning to the base, a liquid hydrogen tanker had to be vented twice. The cause of the overpressure was a malfunctioning scale which allowed a slight overload of hydrogen. [Zalosh and…
This near-miss occurred at a company producing compressed gas bottles according to customers requests. When preparing a gas mixture containing oxygen and nitrogen, by mistake hydrogen was added,…
At an off-site LH2 fill station, a LH2 trailer hit the GH2 purge shut-off valve handle. The tubing attached to the purge valve was bent on both ends but did not leak. [Ordin, NASA (1974)]
During a welding operation on a LH2 fill line it was discovered that LH2 was still in the tank although it should have been drained. Hence the potential for a major explosion existed. [Ordin, NASA…