LH2 leak from a stationary tank
A leak occurred near the bottom of a stationary liquid hydrogen tank with a capacity of a 6,000-gallon. The leak was localised on a valve and was visible due to the air condensation forming white clouds rosing upward and dissipating. Ignition did not occur. Fire fighters tested hydrogen concentration in air around the leaking place and determined it to be safe. After which, plant workers shut off a secondary valve, isolating the leaking valve. Preliminary investigations indicated that a faulty O-ring may have been the cause.
Event Date
December 23, 2013
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

Nothing is known on the ROOT CAUSE. The fact that the leak was identified first at the bottom of the tank, and later also from the top of the tank (see reference), suggest a possible degradation of the thermal isolation capacity of the external shell of the tank. But it cannot be confirmed by unavailability of the investigation report.