A road transportation incident. A road tanker of hydrogen overturned and caught fire.

The incident affected a hydrogen gas purification unit of a chemical plant. A hydrogen release and ignition occurred at the joint between a pressure gauge attached to the inlet piping of an…

A hydrogen leak occurred from a screw connection of a pressure gauge installed on the hydrogenation pre-feeder line alcohol production plant. Due probably to static electricity, the hydrogen…

A fire occurred at a hydrogen refuelling station for buses. The incident was initially reported as an explosion due to a loud noise and vibrations felt in nearby buildings. However, subsequent…

The incident occurred at an ammonia production plant. The plant was starting, when a section of piping between the secondary reformer and a waste heat boiler (“transition pipe”) ruptured. Process…

Fire in a ammonia plant. The accident starts with a leak of a hydrogen-nitrogen mixture at the suctionflange of a compressor. The mixture ignites on contact with air and the fire spreads to an oil…
During repairs of a heat exchanger in a benzene plant, a mixed gas (methane and hydrogen) contained in the cold box attached to the exchanger leaked and caught fire from a welding spark. The…
A fire broke out following a hydrogen leak on the Cyclododecane unit in a chemical plant. A plume of smoke became visible outside the site. The fire was brought under control by putting the unit in…
Hydrogen and butyl acetate released and caught fire on the vent of a hydrogenation reactor, part of a dyes manufacturing plant. The pressure inside the reactor increased due to excess hydrogen…

The fire developed on one of two naphtha crackers for the production of ethylene. The rupture of the reactor made that the hydrogen, petroleum products (benzene) and the pyrophoric catalyst came…

The event occurred on a hydrogen pipe of a sodium chlorate plant. The on-duty field technician noticed a self-sustained ignition on the pipe. The flare-like flame of less than one metre in height was…
The fire occurred in a unit to produce hexamethylenediamine, an organic compound precursor of polymers (HMD). The process is based on the hydrogenation of a precursor in presence of a catalyst. A jet…
In an chlorine production plant, vented chlorine and hydrogen, auto ignited when the hydrogen concentration was allowed to exceed 5% and the mixture mixed with air. [Zalosh and Short, 1978]
The event occurred at the flanges on the outlet of a desulphurization reactor, which was working under about 300 degrees C. The flanges and bolts were cooled down by a large amount of rainwater which…
A fire started in a refinery's gas oil desulphurization unit. The purpose of this unit is to separate sulphur from hydrocarbons and to do so, the latter are raised to 340°C in the presence of…
A jet flame occurred in a diesel distillation unit. It was caused by the release and ignition of hydrogen from the low-pressure (60 bar) section of a the unit. It occurred during maintenance works…
the fire was detected by an employee during the normal inspection tour. It was caused by the ignition of a leak of process gas (hydrogen, methane and water vapour) from the reforming furnaces. The…
A jet fire occurred on the ammonia production unit, caused by a leak on a hydrogen pipe. Hearing a strange noise, an employee triggered the alarm after having discovered an ignited jet of hydrogen.…
Leak from faulty hydrogen seal ignited by short circuit between inboard slip ring and outboard slip ring radial lead connection. Hydrogen flame caused damage to brush gear assembly and inboard slip…
An isolation failure in starter coil of the high voltage generator induced an electric arc to the hydrogen supply line, with consequent fire and melting of the line. [Zalosh and Short, 1978]