Fire in a chemicals plant (341)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire in a chemicals plant

The event occurred on a hydrogen pipe of a sodium chlorate plant. The on-duty field technician noticed a self-sustained ignition on the pipe. The flare-like flame of less than one metre in height was located in the space above the plant control room right above the exit door. The technician signalled an alarm to the plant control room where the field operator immediately informed the shift supervisor and also the regional emergency response centre. The other people on the site took fire extinguishers from the control room and rushed to the fire scene. When opening, from the outside, the door leading to the space above the control room, they noticed that the leak was located right at the door. Even though they discharged two extinguishers to suppress the fire, it did not go out. After that, they shut down Plant-1 using the emergency stop function. Plant-3 and Plant-4 were similarly shut down. During the shutdown, fire fighters dragged a fire hose up onto the landing on which the fire, now dying down, was fully extinguished. The post-accident analysis of the components detected pulverised rust dust inside the removed pipe section. The metal of the corroded section had completely softened, and the connector piece could be removed by pulling by hand. To determine the cause of the hydrogen ignition, the potential differences across the pipe were measured using a voltage meter. No potential differences were detected, so the only conceivable cause of ignition was charged particles, e. g. snowfall early in the morning. Hydrogen appeared to have leaked out from the leak site for an extended period of time, until an igniting factor was introduced.
Event Date
November 29, 2004
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was a leak from a hydrogen pipe, due to corrosion. Hydrogen appeared to have leaked out from the leak site for an extended period, until an igniting factor was introduced. Ignition could have happened due to electrostatically charged particles (snow). ROOT CAUSE was an organisational cause: shortcomings in service and maintenance allowed advancement of the pipe corrosion till when it was not able to bear the internal pressure. An important fact was the absence of sensors which would have been able to detect soon the leaking hydrogen. This highlights a lack of a risk assessment based on worst scenarios and the failure to take measures to prevent them.
Facility Information
Application Type
Application
Pharmaceutical production
Specific Application Supply Chain Stage
Components Involved
Hydrogen pipe in a sodium chlorate plant
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

3 production lines were shut down.

Event Nature
Emergency Action
1. Staff on the site tried to extinguish the fire by means of fire extinguishers, unsuccessfully. 2. Plant-1 was then shut down using the emergency stop function. 3. Plant-3 and Plant-4 were similarly shut down. 4. Fire fighters dragged a fire hose up onto the landing on which the fire, now dying down, was fully extinguished.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

HSE reporting a confidential report