Fire from pressure gauge screw connection in a chemical plant
A hydrogen leak occurred from a screw connection of a pressure gauge installed on the hydrogenation pre-feeder line alcohol production plant. Due probably to static electricity, the hydrogen ignited. The cause of the leak was a dent on the pressure gauge's seat, where erroneously an aluminium gasket was installed together with a copper gasket. Since the regular inspection in October 2014, the aluminium metal had to be replaced by a copper one, but instead of the replacement, a copper gasket had been applied on top of the aluminium one.
Event Date
September 3, 2015
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The INITIATING CAUSE was a damaged metal gasket unable to stand the internal hydrogen pressure. The ROOT CAUSE was a mistake occurred during the last maintenance, possibly in combination with unclear instructions. The operator may not have realised that the aluminium gasket was still sitting in the joint seat, when he mounted the new copper gasket. On top of that, the aluminium gasket was damaged, probably due to the difficult operation of extracting it after use.