Fire from pressure gauge screw connection in a chemical plant (1174)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire from pressure gauge screw connection in a chemical plant

A hydrogen leak occurred from a screw connection of a pressure gauge installed on the hydrogenation pre-feeder line alcohol production plant. Due probably to static electricity, the hydrogen ignited. The cause of the leak was a dent on the pressure gauge's seat, where erroneously an aluminium gasket was installed together with a copper gasket. Since the regular inspection in October 2014, the aluminium metal had to be replaced by a copper one, but instead of the replacement, a copper gasket had been applied on top of the aluminium one.

Event Date
September 3, 2015
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was a damaged metal gasket unable to stand the internal hydrogen pressure. The ROOT CAUSE was a mistake occurred during the last maintenance, possibly in combination with unclear instructions. The operator may not have realised that the aluminium gasket was still sitting in the joint seat, when he mounted the new copper gasket. On top of that, the aluminium gasket was damaged, probably due to the difficult operation of extracting it after use.

Facility Information
Application Type
Application
hydrogenation reactor
Specific Application Supply Chain Stage
Components Involved

scew connection, gasket

Storage/Process Medium
Location Type
Location description

DESCRIPTION of the CHEMICL PROCESS The facility where the leak occurred was a 1,6-hexanediol manufacturing production unit. 1,6-hexanediol is an organic compound with the formula (CH2CH2CH2OH)2. It is industrially made by the hydrogenation of adipic acid or its esters [Wikipedia, https://en. wikipedia. org/wiki/1,6-Hexanediol] GASKET MATERIAL HISTORY When the 1,6-hexanediol manufacturing facility first began operations, copper gaskets were used for metal joints, but they were later replaced by aluminium gaskets. The reason for the change was unclear. The aluminium gaskets stuck onto the receiving seat, making them difficult to remove. Therefore, in October 2014 they were changed to copper gaskets, which have a proven track record.

Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Event Nature
Emergency Action

none

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

KHK accidentl database, incident 2015-308: https://www. khk. or. jp/Portals/0/resources/activities/incident_investigation/hpg_incident/pdf/2015-308. pdf (accessed may 2025)

KHK accidentl database, incident 2015-308: Enghlish version of the Japanese original, based on Google machine translation