Fire in a chlorine production plant

In an chlorine production plant, vented chlorine and hydrogen, auto ignited when the hydrogen concentration was allowed to exceed 5% and the mixture mixed with air. [Zalosh and Short, 1978]
Event Date
January 23, 1968
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE was the formation of a chlorine-hydrogen flammable mixture in the vent. The excess of hydrogen concentration in the exhaust occurred because the hydrogen detector was not (properly) calibrated. The ROOT CAUSE was a failure to apply sound routines for the calibration of instruments.
Facility Information
Application Type
Application
Chlorine production
Specific Application Supply Chain Stage
Components Involved
chlorine electrolyser, exhaust system, gas detection
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

Material damage was 6000 $

Event Nature
Release Type
Release Substance
CL2 H2