Fire in a desulphurisation unit of a refinery (730)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire in a desulphurisation unit of a refinery

The event occurred at the flanges on the outlet of a desulphurization reactor, which was working under about 300 degrees C. The flanges and bolts were cooled down by a large amount of rainwater which had got into the rain-cover around the flanges. This caused the material to shrink and made the flanges too tight, putting too much stress on the ring gaskets which deformed and damaged. As a result, hydrogen gas and light oil mist leaked out and ignited spontaneously, causing damage to pressure gauges and insulation of pipes.
Event Date
July 30, 1998
Record Quality Indicator
Region / Country
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
INITIATING cause was a too high thermo-mechanical stress on flange of a reactor, due thermal gradient induced by rain water. Possible ROOT CAUSES could be an inadequate risk assessment or safety design, and inadequate operative processes, which failed to protect the installation from rain.
Facility Information
Application Type
Application
Hydrodesulphurisation process
Specific Application Supply Chain Stage
Components Involved
hydro-desulphurization unit, flanges and gaskets
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
The operative condition were as usual, but there was a heavy rain several hours before the accident, and a large quantity of rainwater flowed in between the rain cover and the heat-insulating sheet metal.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Property Loss (onsite)

100000

Post-event Summary

A pressure gage and piping heat insulation were damaged by fire.

Lessons Learned
There are many cases where insufficient attention is paid to the specific locations of each valve, and its possible lifetime damage patterns. It is only after that an incident took place, that plant management realises the inadequacy of installations.
Event Nature
Emergency Action
The fire was extinguished by company's own fire fighters.
Release Type
Release Substance
H2, light oil
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Originally in RISCAD. Now in the JST Knowledge Failure Database: https://www. shippai. org/fkd/en/cfen/CC1200030. html (accessed Dec 2023)