Fire in a desulphurisation unit of a refinery
The event occurred at the flanges on the outlet of a desulphurization reactor, which was working under about 300 degrees C. The flanges and bolts were cooled down by a large amount of rainwater which had got into the rain-cover around the flanges. This caused the material to shrink and made the flanges too tight, putting too much stress on the ring gaskets which deformed and damaged. As a result, hydrogen gas and light oil mist leaked out and ignited spontaneously, causing damage to pressure gauges and insulation of pipes.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
INITIATING cause was a too high thermo-mechanical stress on flange of a reactor, due thermal gradient induced by rain water. Possible ROOT CAUSES could be an inadequate risk assessment or safety design, and inadequate operative processes, which failed to protect the installation from rain.