Fire from the storage area of a HRS (1163)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire from the storage area of a HRS

A fire occurred at a hydrogen refuelling station for buses. The incident was initially reported as an explosion due to a loud noise and vibrations felt in nearby buildings. However, subsequent investigations clarified that the fire resulted from a hydrogen venting through a safety valve of the station hydrogen storage. The fire was extinguished within approximately 50 minutes, and no casualties were reported. Some damage occurred to the roof of the storage building.

Event Date
December 27, 2024
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments

The INITIATING CAUSE of the fire was a hydrogen venting through the safety valve. The ROOT CAUSE is uknown (a plausible hypothesis could be a premature activation of a safety device, but it needs to be confirmed).

Facility Information
Application Type
Application
CHG2 storage
Specific Application Supply Chain Stage
Components Involved

safety valve

Storage/Process Medium
Location Type
Location description

DESCRIPTION OF THE FACILITY HRS compression and storage capacity of 180 kg/h with two refueling lines providing 90 kg/h each. designed for commercial vehicles like trucks and buses (https://fuelcellsworks. com/2024/10/14/fuel-cells/korea-busan-new-port-completes-first-hydrogen-refueling-station-for-cargo-trucks). From the pictures of the YTN video, the station storage system seems to consist in hydrogen tube trailers, wit the typical vent system for each of the tube releasing hydrogen inside the building. Another type of longer tubes is visible aswell. The building appears to be only partially covered by a roof. storage pressure is unknown (possiblyaround 40 MPa), the hydrogen inventory, the safety systems in place.

Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (onsite)

low

Post-event Summary

Some damage to the roof structure is visible.

Event Nature
Emergency Action

The fire brigade intervened extinguishing the fire within approximately 50 minutes,

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Collection of news https://cleantechnica. com/2025/01/16/korean-hydrogen-explosions-leaks-auction-failure-impeachment-may-cause-pivot/ https://www. hydrogeninsight. com/transport/safety-concerns-grow-after-two-explosions-at-south-korean-hydrogen-filling-stations-in-same-week/2-1-1759496 https://m. ytn. co. kr/en/news_view. amp. php?param=0115_202412272305332906 (accessed January 2025)