Skip to main content

HIAD Specific Application Supply Chain Stage: Hydrogen Storage


A compressed gas spherical vessel failed along the along the weld, releasing the whole content, consisting in a H2-CH4-rich mixture (54%, 26%). The cause was stress corrosion accelerated by hydrogen.

hydrogen gas cylinder explosion and subsequent fire in an electrical products company. 3 fatalities and 8 injuries. [Note of the validator: while the majority of the news report as cause the…

[NOTE of HIAD Validator: the sources are not completely clear in describing the system involved in this incident ; the following is the most plausible option ] The explosion happened in two hydrogen…
Release from a compressed hydrogen bottle used to fill balloons. The release was followed by ignition and perhaps fast deflagration. Nine people affected, including the operator of the bottle.
The event early on a Saturday morning, when the plant was thus practically empty. Nevertheless, the chronology of the accident can be reconstructed from the testimonies of the few operators who were…
A hydrogen jet fire occurred on a 25m3 tank while transferring a catalyst to a buffer tank. The constabulary created an area of safety around the plant while the staff extinguishes the fire by…
The explosion occurred in a plant for the production of butter. It was due to the rupture of a hydrogen tank, during a sterilisation process at high temperature (so-called UHT treatment). Two…

Hydrogen as carrier gas was provided to a reactor gas chromatograph by several compressed hydrogen bottles. The bottles emptied rapidly, but the loss of carrier gas could only be detected when the…

The accident took place when replacing a pallet of empty hydrogen cylinders with a new full one. The pallet in service (almost empty) was not disconnected from the gas supply line. When the operator…
A 50-litre standard hydrogen gas cylinder was temporarily placed and used in a laboratory. The hydrogen gas was used for a flame ionization detector (FID) in gas chromatography (GC) instrument. The…
The release affected a stationary hydrogen storage consisting of a cryogenic vessel at a manufacturing facility. The A burst disc opened releasing hydrogen through a vent stack located between…
A hydrogen leak occurs at a gas cylinder storage tank park in a nuclear power plant. Employees locate the origin of the leak on a defective pressure regulator. They isolate the hydrogen release and…
Release from a compressed storage of an optics component plantThe leak was observed on the hydrogen storage consisting of 19 racks of 16 cylinders each. Rescue teams set up a security perimeter and a…
A leak occurred on a relief valve of a high pressure hydrogen storage tank. No explosion or fire occurred.

The incident occurred at a plant manufacturing polymer batteries, audio and GPS systems. As consequence of the great tohokyu earthquake and tsunami, a pipe of a hydrogen tank started leaking,…

A hydrogen tank exploded and caught fire at a chemical plant.

Hydrogen caused an explosion at a power plant, killing two people and injuring 13 others. The station was subsequently shut down. The cause of the explosion was not reported. At first, sources…

A leak developed on a main connector to a pallet consisting of 12 hydrogen bottles, which had not been re-tightened for a few weeks. The alarm, at at 5% of the LEL, went off , with automatic call…

A large hydrogen gas leak from a dewar resulted when bolts holding fitting the top of the tank was loosened. The fitting contained instruments. On loosening the third bolt, hydrogen gas excaped…

A leak occurred at the fill valve of a LH2 vessel. With the tank pressure at about 100 psi a leak was noticed. The area was cleared and the vessel was emptied by remote controls. [Ordin, NASA…