Hydrogen release from a liquid hydrogen tank
The release affected a stationary hydrogen storage consisting of a cryogenic vessel at a manufacturing facility. The A burst disc opened releasing hydrogen through a vent stack located between approximately at 5-6 m above ground. The cryogenic hydrogen storage tank had an insulation jacket, but it had been idle for a long time. Therefore, the heat transfer through the tank insulation had caused the evaporation of liquid hydrogen enough to increase the pressure beyond the design pressure of the burst disc. After the opening of the burst disc, the hydrogen was released to the environment through the stack without further consequences. It did not ignite. Approximately seven months after the replacement of the burst disc, the new burst disc prematurely ruptured for the same reason.
Event Date
April 5, 2008
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIAL CAUSE was a natural increase of the internal pressure of the cryogenic tank. The burst disc and the venting system operated safely and as expected . The fact that the tank was left idling without inspection suggests that operator thought that the vacuum jacket eliminated the heat transfer, while in reality, it only reduced it. The ROOT CAUSE is probably related to lack of maintenance and/or of knowledge of the operation of a cryogenic tank.