Hydrogen release and ignition at the gas storage station of a nuclear power plant.
The accident took place when replacing a pallet of empty hydrogen cylinders with a new full one. The pallet in service (almost empty) was not disconnected from the gas supply line. When the operator in charge of handling (fork lift) begun to remove the pallet in service from its position, he teared off the hose connecting it to the pressure relief system. The pressurised hydrogen in the pipes and in the pallet escaped and ignited. The intervention of the teams from the plant and external emergency services extinguished the fire in 1h45.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause is a wrong application of the procedure of replacing gas cylinders. There are however several contributing causes (uncontrolled access to the storage area, non respecting of the ATEX distance for welding work, abnormally high frequency to replace the gas pallets, etc. ). The root cause lies therefore in the lack of adaptation of the safety operation to the temporary different working conditions.