Leak from a CGH2 stationary storage
A leak developed on a main connector to a pallet consisting of 12 hydrogen bottles, which had not been re-tightened for a few weeks. The alarm, at at 5% of the LEL, went off , with automatic call directly to the local fire brigade, which came onsite. An employee with knowledge of the gas system got an automatic sms notification and also came onsite The first responders waited until the gas concentration went down, dispersed by the wind, and then closed the connection.
Event Date
June 26, 2023
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITIATING CAUSE was the release of hydrogen from a connection not properly tightened. The ROOT CAUSE was probably the lack of effective regular inspection. It it unclear if the fact that the leack occurred during the hottest day of the year could have plaid a role.