An explosion occurred at a hydrogen boiler of a chemical manufacturing plant producing hydrogen gas and other substances. A potential flow restriction in the feed line to a hydrogen-fired boiler…
Test facility H2 vent line exploded destroying about 150 feet of line. The flare stack was on at the time. [Ordin, NASA (1974)]
A hydrogen leak occurred on a hydrogen and fuel cells bus when in service. The bus driver received a low hydrogen level alarm [Note of HIAD validator: the nature of the alarm is not further…
The event occurred during a pressure testing of a LH2 pump discharge system. A weld joint failed at an internally tied bellows. The weld failed at 1100 psi (ca. 76 bar) while the test pressure…
The second stage of the Saturn V (S-II-T) was under full-duration static test, when one fire near LH2 valves of the LH2 tank and another in the engine area caused the automatic termination of the…
During a leak check of a flash point material testing chamber, the chamber was inadvertently over-pressurised with GH2. The glass port in the door burst, causing damage to the chamber and to the…
During the pre-launch checkout, a check valve failed in the "open" position and an accidental venting of liquid hydrogen occurred. The event caused an unscheduled check and replacement…
During the development test of a booster, a 3000 psig (ca. 205 bar) relief valve actuated at the normal line pressure releasing gaseous hydrogen, which ignited, resulting in an explosion which…
An unscheduled venting of a stage LH2 tank occurred, creating a hazardous condition for personnel and creating a potential explosion/ fire. [Ordin, NASA (1974)]