Internal explosion of a vent line (398)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Internal explosion of a vent line

Test facility H2 vent line exploded destroying about 150 feet of line. The flare stack was on at the time. [Ordin, NASA (1974)]

Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments

The line had not been properly purged after removing and installing a vent valve in the system. Ignition of the hydrogen-air mixture occurred either from flare stack or from static charge.

Facility Information
Application Type
Application
material testing
Specific Application Supply Chain Stage
Components Involved

vent

Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary

The vent line had been earlier maintained, by re-installation of a vent valve. It is unknown if the incident occurred during testing or shutdown venting.

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (offsite)

0

Post-event Summary

Only part of the vent line was destroyed.

Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
References
References

Mishap no 58 in P. L. Ordin, Review of hydrogen accidents and incidents in NASA operations, 1974, NASA TM X-71565 https://ntrs. nasa. gov/citations/19740020344

Lowesmith et al. , Safety issues of the liquefaction, storage and transportation of liquid hydrogen: An analysis of incidents and HAZIDS, Int. J. Hydrogen energy (2014) https://doi. org/10. 1016/j. ijhydene. 2014. 08. 002

Hankinson and Lowesmith, Qualitative Risk Assessment of Hydrogen Liquefaction, Storage and Transportation, FCH JU project IDEALHY, Deliverable 3. 10 (2013) confidential (accessed October 2025)