Internal explosion of a vent line
Test facility H2 vent line exploded destroying about 150 feet of line. The flare stack was on at the time. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The line had not been properly purged after removing and installing a vent valve in the system. Ignition of the hydrogen-air mixture occurred either from flare stack or from static charge.