Ignited hydrogen leak at an aerospace testing facility

The event occurred in a university research building dedicated to the study of the take-off of space launchers . An operator gave the alarm during the hydrogen pressure pre-setting phase. he had seen on the video surveillance screen a flame at a pressure regulator on the line located on the walkway above the test hall. One of the operators closes the supply line and triggers the purge. According to the ARIA report, two combined equipment failures caused the damage: - a hydrogen leak on the pressure regulator; - an electrical short circuit on one of the equipment in the environment near the regulator. The latter was caused either by a material defective of a system temporarily installed on the bridge for experimentation, either by over-voltage due to accumulation of moisture in one of the elements of the electrical circuit following a water leak the day before.
Event Date
March 6, 2018
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the combination of the technical failures, (the pressure regulator leak and short-circuit on an equipment). The root cause is unknown, but probably related to the operational aspects for a better monitoring/control of materials and equipment.
Facility Information
Application Type
Application
Aerospace
Specific Application Supply Chain Stage
Components Involved
experimental testing laboratory, pressure reducer device
Location Type
Operational Condition
Pre-event Summary
The event occurred during the starting of a test, in the hydrogen pressure pre-setting phase
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

No injury and damage.

Lessons Learned
Probably better procedures for adequate monitoring/control of materials and equipment will reduce probability of occurrence of this type of incident.
Event Nature
Emergency Action
The alarm was given by an operator. On-site officers contained the fire.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Flame Type
References
References

Event description in the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/51294/ (accessed September 2020)