Relief valve opening
During the development test of a booster, a 3000 psig (ca. 205 bar) relief valve actuated at the normal line pressure releasing gaseous hydrogen, which ignited, resulting in an explosion which damaged the test facility. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The IMMEDIATE CAUSE was the premature activation of the pressure relief valve. This was due to the improper setting of the activation pressure. The ROOT CAUSE was inadequate inspection and a CONTRIBUTING CAUSE was a poor design of the venting system which was installed in a horizontal position causing inadequate venting and build-up of static electricity.