HIAD Facility - Application Type: Hydrogen Stationary Storage


Following a loss of power the failure of a backup battery causes an alarm in a hydrogen storage facility. Consequently, a valve on the purge circuit and 30 m3 of hydrogen is released to the…

A Bourdon tube ruptured in pressure gauge after 528 hours of operation in LH2. The alarm sounded, the system was isolated and then vented. [Ordin, NASA (1974)]

A fire and a series of explosions occurred on a petrochemical plant, causing damage to process vessels, containment walls and process utility piping. It is believed that lightning struck a two story…

During the warm-up phase of a large liquid hydrogen sphere, the annular space was over-pressurised and perlite insulation was expelled through the evacuation nozzle and the burst diaphragm. Air…

A large hydrogen vapor cloud was released from the base of a bulk hydrogen storage tank, at special gas company. The cloud found an ignition source producing a large fireball, shook windows in the…

An explosion occurred in a hydrogen storage tank followed by fire.

Hydrogen leak occurred from temporary pipe work during transfer of hydrogen between permanent and emergency cylinders. Ignition source unknown. Resultant explosion caused serious burns to one…

A LH2 tank exploded causing injury and damage when hot wire sensors were used in tank after purging. [Ordin, NASA (1974)]

Fire in bulk hydrogen storage compound. Pressure gauge shut off valve spindle blown out (could be completely unscrewed and removed). The subsequent leak ignited by unknown source. No injuries…
The accident happened during testing of a hydrogen tank at a company which manufactured valves and other hydrogen-storage components. A dull bang and a huge pressure wave was felt kilometres away.…

This incident consisted in the dropping of a gas cylinder and the release of its content due to stress corrosion

The incident occurred during the filling of six bundles of compressed hydrogen cylinders by means of a compressor. Each bundle consisted of 16 cylinders of 40-liter each. When approaching the…

A released occurred at a hydrogen storage system. A small quantity of hydrogen gas leaked out of a pipe and caught fire. The danger of an explosion was averted by the safety crew who put out the fire…
A hydrogen fuel tank release caused a fire at a hydrogen refuelling station. A pressure relief valve installed on one of the 18 storage tanks failed at a pressure far below its design opening value.…
Fires and chain reactions involved more than 100 cylinders of hydrogen or other gases in a storage system. The fire lasted for more than 5 hours and the neighbourhood has been affected by flying…
Employees were refilling a rack of 15 hydrogen cylinders that were connected together on a steel pallet with railings. A leak developed at a valve and the pressurized hydrogen ignited. Operations…
A compressed gas spherical vessel failed along the along the weld, releasing the whole content, consisting in a H2-CH4-rich mixture (54%, 26%). The cause was stress corrosion accelerated by hydrogen.
The release affected a stationary hydrogen storage consisting of a cryogenic vessel at a manufacturing facility. The A burst disc opened releasing hydrogen through a vent stack located between…
Leakage of gas from blow-off pipe for depressurization while filling hydrogen in cylinder.

A leak occurred near the bottom of a stationary liquid hydrogen tank with a capacity of a 6,000-gallon. The leak was localised on a valve and was visible due to the air condensation forming white…