Fire - hydrogen
The incident occurred during the filling of six bundles of compressed hydrogen cylinders by means of a compressor. Each bundle consisted of 16 cylinders of 40-liter each. When approaching the final filling pressure, the bottom of one of the 40-liter containers was suddenly separated and ejected from the cylinder, with consequent high-pressure hydrogen release, explosion and fire. The recoil reaction of the gas displaced the cylinder bundle causing an additional leak at filling manifold piping, so that the bundles were engulfed in flames on both side. The slate roof of the building was blown off by the shock wave caused by the cylinder rupture. The post-incident investigation found that moisture had seeped in from the compressor and accumulated at the bottom of the container, causing corrosion pits, and that the cycling stress due to repeated filling had caused cracks to progress from the inside and reach a position 1 to 1. 5 mm from the outer surface.

The INITIATING CAUSE was the sudden failure of the whole cylinder due to fatigue and corrosion. The ROOT CAUSE was the incapacity to foresee and to detect a structural degradation of the high-pressure component progressing from inside (thus invisible to visual inspection). The corrosion and the consequent corrosion -assisted crack growth was caused by contaminants coming from the compressor. This reveal a lack of operative quality assessment and an overall risk assessment able to consider the whole connected system, and not just the risks related to each of the components individually.