Damage to the insulation sell of a LH2 tank
During the warm-up phase of a large liquid hydrogen sphere, the annular space was over-pressurised and perlite insulation was expelled through the evacuation nozzle and the burst diaphragm. Air had leaked into the annular space some weeks earlier and repairs had been carried out. However, the air had solidified in the annular space. During the warm-up, the air vaporised and caused a pressure build-up. The vessel sustained minor damage. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

Leak points had been found in the external shell and sealed approximately six weeks prior to this event. The event was due to a lack of design considerations for monitoring/ evaluating the tank conditions during warmup. The hazards involved in making temporary repairs in the evacuation system were not identified. Therefore, the ROOT CAUSES were shortcoming in repairing procedures and n asesing the related risks.