A hydrogen leak occurred on a makeup gas line of a gas oil hydrotreater unit of a refinery. The release location was a 1-inch gate valve, which later was found 10% open and with no bull plug. The…
A truck-trailer carrying compressed hydrogen cylinders stopped on an highway and reported a hydrogen leaking from the cylinders. The highway was immediately closed in both directions. When the fire…
A sudden failure occured on a hydrogen line of a refinery desulphurisation unit. The equipment was located between a hydrogen compressor and its overpressure protection valve. It was equipped with an…
During maintenance work on a gas pipeline carrying hydrogen , a worker hears a leak at about at a bridge. The operator measures an concentration of 3% of the low flammability limit at few centimetres…
This incident occurred on a hydrogen production device during the Great Hanshin Earthquake (Hyogo Prefecture Southern Earthquake). Hydrogen gas leaked from a pipe thread joint in a valve station. The…
The release occurred in the hydrogen storage system of a refuelling station. In the night a leakage occurred at one of the 120 high pressure bottles (800 bar). The leakage occurred at a screwed…
Malfunctioning of the non-return valve of the hydrogen compressor has caused the pressure between the hydrogen bottle and the compressor to rise to the maximum allowed pressure of 275 barg. As a…
A factory was evacuated after a tank began leaking hydrogen. No injuries were reported
Compressed hydrogen was released from a storage system due to the rupture of a Bourdon-type pressure gauge. [Zalosh and Short, 1978]
A hydrogen leak took place on a trailer carrying compressed hydrogen, located inside the fenced perimeter of a hydrogen station. According to the company managing the hydrogen delivery and refuelling…
A liquid hydrogen tanker was travelling on a highway, when the driver noticed vapour exiting the rear tanker cabinet. The driver stopped the vehicle in a safe location and discovered that the vapour…
A truck carrying 6,000 gallons of liquid hydrogen (1,600 kg) experienced an accidental loss of confinement while travelling. The truck driver noticed a white vapour cloud coming from the rear of his…
The incident happened during a liquid hydrogen delivery at a customer site. When the drivers were pressuring up the tanker for product transfer, the safety relief system rupture disc failed…

A faulty rupture disc failed prematurely releasing 750 cu ft of hydrogen (0. 2 kg). [Zalosh and Short, 1978]

The vacuum on a liquid hydrogen tanker was lost, resulting in a hydrogen release, both manually and through bursting of burst disc [Zalosh and Short, 1978]

A faulty burst disc on a liquid hydrogen tanker failed prematurely releasing 750 cu. ft. of of hydrogen. [Zalosh and Short, 1978]

Due to a loss of confinement of the inner shell of the liquid hydrogen tank, the vacuum of the external shell was destroyed. The reduced thermal insulation capacity of the shell caused evaporation…

The vent valve on a liquid hydrogen tanker vibrated open allowing a slight discharge hydrogen. [Zalosh and Short, 1978]

An unexplained loss of vacuum resulted in the release of all the transported hydrogen by manual venting and and opening of the relief valve. [Zalosh and Short, 1978]

A LH2 trailer was preparing to unload, when the pressure in the tank rose to about 165 psi (11. 3 bar) and caused the burst disc to rupture. The whole tank content was vented to atmosphere.