Release from a hydrogen line to the desulphurization unit of a refinery
A sudden failure occured on a hydrogen line of a refinery desulphurisation unit. The equipment was located between a hydrogen compressor and its overpressure protection valve. It was equipped with an automatical isolation system, however, the failed pipe, located at the bottom of the system, was without self-draining mechanism. . The bursting of the pipe was due to its corrosion: a large loss of thickness extended over 300 mm. The presence of a bend at a low point on a line without circulation led to the accumulation of deposits initiating a corrosion mechanism.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
INITIATING CAUSE was corrosion which reduced the stress-bearing wall thickness of the pipe. The ROOT CAUSE was found in a non-optimal design, failing to identify and taking care of weak points on the line.