Release from a hydrogen truck (1055)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Release from a hydrogen truck

A hydrogen leak took place on a trailer carrying compressed hydrogen, located inside the fenced perimeter of a hydrogen station. According to the company managing the hydrogen delivery and refuelling station, the leak did not pose any risk to people or the environment. A preliminary assessment identified a faulty valve source of the leak, but it was unclear at that time if it was a single defect or a systemic (i. e. design) problem. Following a detailed investigation in close cooperation with the trailer and valve suppliers, the company determined that the root cause of the valve malfunction was due to a set of improperly tightened bolts, causing an O-ring to burst. Approximately one month later, addtional malfunctioning were found on the same valves on othr eight trailers.
Event Date
June 10, 2023
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE The was a non-further specified defective valve. The assembly error was not detected by valve supplier quality control nor by the tube trailer suppliers’ quality inspection, but only when the all assembly was operating. This, and the fact that more valves were found defective, suggest as ROOT CAUSE an improper tightening procedure damaging the O-ring , an installation error or a manufacturing defect.
Facility Information
Application
CGH2 tube trailer
Specific Application Supply Chain Stage
Components Involved
O-ring, bolts (presumaby from a flange), compressed hydrogen tube
Storage/Process Medium
Storage/Process Quantity
1000
Actual Pressure
30
Design Pressure
30
Location Type
Location description
DESCRIPTION OF THE UNIT Various wesites provide the following technical data : Capacity = 1,100 kg of hydrogen Nominal pressure = 30 MPa 129 onboard type 4 compressed hydrogen cylinders, mounted vertically in racks and connected via piping and a shut-off valve. The trailers can be used as swap modules into the company hydrogen refuelling stations using or as delivery to customers.
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (onsite)

low

Post-event Summary

The company decided to suspend the use of its 12 hydrogen trailers until all relevant valves have been controlled. The grounding of the trailer fleet had a negative impact on the distribution of hydrogen to customers and refuelling stations. Following verification that the fault was not systematic, the company redeployed the trailers. Mitigating actions will be implemented at both trailer supplier and valve supplier to eliminate recurrence of the near miss.

Event Nature
Emergency Action
The company safety strategy to detct leak is unknown.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Hydrogen insight news of 21 June 2023: https://www. hydrogeninsight. com/transport/everfuel-halts-supply-to-its-hydrogen-refuelling-stations-after-h2-leak-discovered-in-truck-trailer/2-1-1471760 a(accessed 22 June 2023)

Transport Company statement 17/07/2023 https://www. everfuel. com/news/everfuel-update-on-hydrogen-trailer-fleet/#:~:text=July%2017%2C%202023%20%7C%20Press%20releases,cause%20for%20the%20end%2Dcustomers. (accessed October 2025)

Hydrogen insight news update of 21 June 2023: https://www. hydrogeninsight. com/transport/everfuel-halts-supply-to-its-hydrogen-refuelling-stations-after-h2-leak-discovered-in-truck-trailer/2-1-1471760 a(accessed 22 June 2023)

Hydrogen insight news update of 27 June 2023