Release from a hydrogen storage
Malfunctioning of the non-return valve of the hydrogen compressor has caused the pressure between the hydrogen bottle and the compressor to rise to the maximum allowed pressure of 275 barg. As a consequence, as foreseen by the safety system, the rupture disc of the safety valve broke and the hydrogen content of the gas bottle and the pipe section involved has been released through the vent above the roof of the building. The released hydrogen ingited and a flame could be seen for some instants. Ignition could have been caused by the occurrence of the following events: - Expansion of hydrogen at the end of the exhaust pipe, - Consequent mixing of hydrogen and air up to a near-stoichiometry and increase of gas temperature - Mixture ignition due to sparks from static electricity potential generated by gas molecules friction against suspended dust particles.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The INITIATING CAUSE was the intenral leaking of the return valve of the compressor. The fact that that valve, after dismantling and cleaning, functioned as designed, suggested a ROOT CAUSE in the lack of regular maintenance. The fact that a flame could develop at only 2. 5 m above ground made the operator realise a shortcoming of the risk assessment and the related safety design.