HIAD Nature Event - Ignition Source: Unknown


A hydrogen fuel tank release caused a fire at a hydrogen refuelling station. A pressure relief valve installed on one of the 18 storage tanks failed at a pressure far below its design opening value.…
A tanker was travelling on a highway, when a passing motorist notified a problem with the tanker to the drivers. They pulled the unit safely off the highway, went to rear of the tanker and opened the…
The truck was delivering hydrogen to a steel products plant. It contained approximately 8500 gallon of liquid hydrogen. The operation of transfer to the customer tank had just terminated. The fire…

A liquid hydrogen tanker was preparing to transfer hydrogen to a stationary tank belonging to a manufacturing facility. The tanker was being pressurised before transfer, when a burst disc failed…

A fire occurred at a non-further specified indsutrial plant. The fire was the consequence of a liquid hydrogen leak from a joint between an isolating block valve and a relief valve on one of the…

The chain holding compressed hydrogen cylinders on a lorry broke. Probably the cylinders fell and due to the mechanical impact they released hydrogen resulting in a small fire [Zalosh and Short,…

This incident occurred at a reactor at a succinic acid manufacturing plant. The reactor was had just terminated the hydro-generation of maleic anhydride for manufacturing succinic acid. Hydrogen…

A vehicle (non-further specified) carrying two hydrogen gas cylinders had to brake suddenly. The two cylinders tipped over, damaging the valve and causing hydrogen gas to leak out and ignite. The…

A road transportation incident. A road tanker of hydrogen overturned and caught fire.

The incident affected a hydrogen gas purification unit of a chemical plant. A hydrogen release and ignition occurred at the joint between a pressure gauge attached to the inlet piping of an…

A fire occurred at a hydrogen refuelling station for buses. The incident was initially reported as an explosion due to a loud noise and vibrations felt in nearby buildings. However, subsequent…

Fire in a ammonia plant. The accident starts with a leak of a hydrogen-nitrogen mixture at the suctionflange of a compressor. The mixture ignites on contact with air and the fire spreads to an oil…
This incident occurred in a unit processing vegetable oils and fats. the explosion occurred in a hydrogenation facility, specifically where hydrogen is processed with a very high-pressure (400 bar).…
The fire occurred in a unit to produce hexamethylenediamine, an organic compound precursor of polymers (HMD). The process is based on the hydrogenation of a precursor in presence of a catalyst. A jet…
Fires and chain reactions involved more than 100 cylinders of hydrogen or other gases in a storage system. The fire lasted for more than 5 hours and the neighbourhood has been affected by flying…
A fire started in a refinery's gas oil desulphurization unit. The purpose of this unit is to separate sulphur from hydrocarbons and to do so, the latter are raised to 340°C in the presence of…
A jet flame occurred in a diesel distillation unit. It was caused by the release and ignition of hydrogen from the low-pressure (60 bar) section of a the unit. It occurred during maintenance works…
the fire was detected by an employee during the normal inspection tour. It was caused by the ignition of a leak of process gas (hydrogen, methane and water vapour) from the reforming furnaces. The…
A jet fire occurred on the ammonia production unit, caused by a leak on a hydrogen pipe. Hearing a strange noise, an employee triggered the alarm after having discovered an ignited jet of hydrogen.…

The incident occurred during maintenance works at a hydro-cracking unit of a refinery (the report does not explicitly mention the unit, but it is plausible to assume that it was a hydro-cracking…