Fire from a LH2 tanker

The truck was delivering hydrogen to a steel products plant. It contained approximately 8500 gallon of liquid hydrogen. The operation of transfer to the customer tank had just terminated. The fire started at the tanker vent stack during post-delivery venting. The emergency services were called - fire engines from two stations attended. The facility and the neighbourhood, including local schools and businesses were evacuated as a precautionary measure. The fire was limited to the tanker vent stack. The hazardous material incident team personnel closed the vent valve the 2. 5 hours later. The emergency services closed the traffic and evacuated several businesses, schools and homes for a few hours.
Event Date
August 29, 2018
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
According to preliminary findings, the INITATING CAUSE was the failure of a valve. The ignition of the hydrogen may have been caused, of facilitated by a lack of proper grounding, through static build-up. The investigation to determine the ROOT CAUSE was not yet terminated at the moment the source issued this event.
Facility Information
Application
LH2 tanker
Specific Application Supply Chain Stage
Components Involved
vent valve
Storage/Process Medium
Storage/Process Quantity
2274
Actual Pressure
1
Design Pressure
1
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Currency
Property Loss (onsite)

47000

Property Loss (offsite)

0

Post-event Summary

There was no release of hazardous materials due consumption by fire. There were no reported injuries or damage to property. The rear of the tanker did incurred some minor fire damage.

Lessons Learned

A picture provided by local news shows that the emergency teams fought the fire by means of a water jet directed to the tank vent. It is in general not advised to use water to stop a fire on a cryogenic tank. The action can cause freezing of the water and the blocking of the pressure relief venting, with consequent building up of the pressure inside the tank and possible catastrophic failure of the entire tank. In this case, however, the LH2 had already been transferred and it could be assumed that the little hydrogen left in the taker was already evaporated or in the process to do so, with negligible potential for a major pressure increase.

Event Nature
Emergency Action
The emergency services were and fire engines from two stations attended. The facility and the neighbourhood, including local schools and businesses were evacuated as a precautionary measure. Although the sources do no report the tactics adopted by the fire-fighting teams, a news picture shows a water jet directed to the place of the fire. The hazardous material incident team personnel closed the vent valve and the 2. 5 hours later. The tanker was inspected by the emergency response teams, declared safe and released to the owner which transported it back to its premises. After that, it was inspected by a 3rd party vendor.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Flame Type
References
References

Incident I-2018100122 and I-2018100262 of the US Pipeline and Hazardous Materials Safety Administration PHMSA: https://portal. phmsa. dot. gov/analytics/saw. dll?Portalpages&PortalPath=%2Fshared%2FPublic%20Website%20Pages%2F_portal%2FHazmat%20Incident%20Report%20Search (accessed September 2024)

Metroforensics news of August 29, 2018 https://metroforensics. blogspot. com/2018_08_30_archive. html (accessed November 2020)

Hard Working Trucks news of August 29, 2018 (accessed November 2020) https://www. hardworkingtrucks. com/explosion-during-hydrogen-tanker-truck-fire-rattles-california-businesses-schools/