Fire from a LH2 tanker during transfer (370)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire from a LH2 tanker during transfer

A liquid hydrogen tanker was preparing to transfer hydrogen to a stationary tank belonging to a manufacturing facility. The tanker was being pressurised before transfer, when a burst disc failed prematurely. The hydrogen ignited at the vent stack. The fire lasted approximately one hour. The emergency responders decided to evacuate the manufacturing facility and a nearby bowling alley. The bursting disc was one of two pressure relief devices protecting the tanker from over-pressurisation. In this sense, even if it failed prematurely, it resulted in a safe situation, with the hydrogen venting via the vent stack and the tank reducing internal pressure. The disc was rated for 210 psig (14. 5) but failed prematurely at approximately 145 psig (ca. 11 bar).

Event Date
March 4, 1995
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIAL CAUSE was the premature failure of a burst disc. In absence of the results of an post-incident investigation, it is impossible to attribute a ROOT CAUSE which could be related to material ageing, or to wrong installation or to a wrong choice of materials.

Facility Information
Application
LH2 tanker
Specific Application Supply Chain Stage
Components Involved

burst disc

Storage/Process Medium
Storage/Process Quantity
3600
Actual Pressure
1
Design Pressure
1
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Currency
Property Loss (onsite)

1500

Property Loss (offsite)

0

Post-event Summary

A negligible amount of hydrogen was released.

Lessons Learned

The safety system worked as expected. The tank was equipped with two independent pressure relief devices, protecting the trailer tank from over-pressurisation. Even if one of the two burst discs failed prematurely, it resulted in a safe situation, with the hydrogen venting via the vent stack and the tank reducing internal pressure.

Event Nature
Emergency Action

The fire was left extinguish by itself. The manufacturing site was evacuate, as well as a neighbourhood.

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Incident I-1995040335 of the US Pipeline and Hazardous Materials Safety Administration PHMSA: https://portal. phmsa. dot. gov/analytics/saw. dll?Portalpages&PortalPath=%2Fshared%2FPublic%20Website%20Pages%2F_portal%2FHazmat%20Incident%20Report%20Search (accessed September 2024)