Fire from a LH2 tanker during transfer
A liquid hydrogen tanker was preparing to transfer hydrogen to a stationary tank belonging to a manufacturing facility. The tanker was being pressurised before transfer, when a burst disc failed prematurely. The hydrogen ignited at the vent stack. The fire lasted approximately one hour. The emergency responders decided to evacuate the manufacturing facility and a nearby bowling alley. The bursting disc was one of two pressure relief devices protecting the tanker from over-pressurisation. In this sense, even if it failed prematurely, it resulted in a safe situation, with the hydrogen venting via the vent stack and the tank reducing internal pressure. The disc was rated for 210 psig (14. 5) but failed prematurely at approximately 145 psig (ca. 11 bar).

The INITIAL CAUSE was the premature failure of a burst disc. In absence of the results of an post-incident investigation, it is impossible to attribute a ROOT CAUSE which could be related to material ageing, or to wrong installation or to a wrong choice of materials.