Fire in the test chamber of a rocket LH2 tank
During preparation of a spacecraft LH2 tank in an environmental test chamber, a liquid hydrogen fire occurred in the chamber. The tank was being "topped off" at the time. Damage was caused to the facility and test system. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

Air had entered the system through the vent line quick disconnects. Ignition occurred as a result of bare wires in the heater access hole. A protective insulation grommet had inadvertently been omitted. The discrepancy had not been identified by inspection. ROOT CAUSES are related to an error in the execution of one preparatory step and in failing to identify it during inspection. Moreover, vent are expected to be designed to avoid or limit as far as possible entrance of air, preventing formation of explosive gas mixture.