Explosion in a fertilisers plant
The accident occurred during the maintenance of a sulphuric acid storage tank in an industry for the fertilizers production. The maintenance works consisted in cutting operations (to remove some plates fastened with bolts) by using oxyacetilenic flame on the storage tank On the internal surface of a tank containing sulphuric acid a corrosion phenomenon associated with the accumulation of hydrogen occurred owing to poor maintenance. The hydrogen was then ignited by the oxyacetylenic flame. The explosion hurled the tank over a hangar, demolishing two other tanks (also containing sulphuric acid) and causing the escape of the product which invaded the basin of containment. The two men who were performing the cutting operation died. The released sulphuric acid evaporated from the basin originating a toxic cloud which dispersed without consequences for the population. The basin invaded by the sulphuric acid was emptied and neutralized with sodium carbonate in order to avoid that sulphuric acid could corrode the ammonia piping inside the basin itself.
Event Date
October 10, 1985
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The accident occurred because, on the internal surface of a tank containing sulphuric acid, a corrosion phenomenon associated with the accumulation of hydrogen occurred due to poor maintenance (caused by inadequate procedures). The hydrogen was then ignited by the oxyacetylenic flame used by two workers for cutting operations.