Skip to main content

Explosion in a fertilisers plant (209)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion in a fertilisers plant

The accident occurred during the maintenance of a sulphuric acid storage tank in an industry for the fertilizers production. The maintenance works consisted in cutting operations (to remove some plates fastened with bolts) by using oxyacetilenic flame on the storage tank On the internal surface of a tank containing sulphuric acid a corrosion phenomenon associated with the accumulation of hydrogen occurred owing to poor maintenance. The hydrogen was then ignited by the oxyacetylenic flame. The explosion hurled the tank over a hangar, demolishing two other tanks (also containing sulphuric acid) and causing the escape of the product which invaded the basin of containment. The two men who were performing the cutting operation died. The released sulphuric acid evaporated from the basin originating a toxic cloud which dispersed without consequences for the population. The basin invaded by the sulphuric acid was emptied and neutralized with sodium carbonate in order to avoid that sulphuric acid could corrode the ammonia piping inside the basin itself.
Event Date
October 10, 1985
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The accident occurred because, on the internal surface of a tank containing sulphuric acid, a corrosion phenomenon associated with the accumulation of hydrogen occurred due to poor maintenance (caused by inadequate procedures). The hydrogen was then ignited by the oxyacetylenic flame used by two workers for cutting operations.
Facility Information
Application Type
Application
Fertilisers production
Specific Application Supply Chain Stage
Components Involved
sulphuric acid storage tank, cutting tool, oxyacetilenic flame
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
The accident occurred during the maintenance of a sulphuric acid storage tank in an industry for the fertilizers production. The maintenance works consisted in cutting operations (to remove some plates fastened with bolts) by using oxyacetilenic flame on the storage tank.
Consequences
Number of Injured Persons
0
Number of Fatalities
2
Post-event Summary

The basin invaded by the sulphuric acid was emptied and neutralized with sodium carbonate in order to avoid that sulphuric acid could corrode the ammonia piping inside the basin itself.

Lessons Learned
Too few details are known to be able to draw a specific lesson learnt from this event. However, this page reports general lessons learnt and the evolution of this type of hazard prevention: http://www. sulphuric-acid. com/sulphuric-acid-on-the-web/Hydrogen-Safety. htm. This report goes well in details of single cases: http://www. sulphuric-acid. com/sulphuric-acid-on-the-web/Acid%20Engineering%20&%20Consulting%20Inc. %20-%20Leonard%20J. %20Friedman. pdf
Event Nature
Release Type
Release Substance
H2, H2SO4
Hydrogen Release Concentration (%)
0.00
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

From public part of MARS database