Skip to main content

Hydrogen fire in a alcohols production plant (905)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Hydrogen fire in a alcohols production plant

The fire occurred after a hydrogen released from a venting valve opened for inspection. The hydrogen was at 300 bar and 300C centigrade and between 200 and 300 bar. The hydrogen ignited probably spontaneously and killed 4 workers and injured additional 3. A similar accident seems to have taken place in the same installation 5 years ago. A safety study of the facility has been requested before the start-up of the plant
Event Date
August 14, 1989
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the manual opening of a valve which released hydrogenThe root causes have not been identified even if a general test of the equipment involved in the fire and/or suspected to have caused the accident was carried out.
Facility Information
Application Type
Application
alcohols production
Specific Application Supply Chain Stage
Components Involved
venting flange reactor(?)
Storage/Process Medium
Actual Pressure
30
Design Pressure
30
Location Type
Location description
DESCRIPTION OF THE PROCESS The hydrogenation unit was part of an organic chemical industry for the production of raw hydrogenated alcohols from vegetable and animal raw materials.
Operational Condition
Consequences
Number of Injured Persons
3
Number of Fatalities
4
Currency
Property Loss (onsite)

2500000

Post-event Summary

4 causalities, 3 injured workers, 2. 5 MEuro damage.

Lessons Learned
An investigation was performed, which however it is not (anymore) publicly available. Logic recommendations would be to improve the venting system to avoid mass release and fire, and to conduct a detailed analysis of previous similar event which seems to have taken place in the same installation 5 years previously (in 1984).
Event Nature
Emergency Action
The isolation valves were shut-off and the Internal Emergency Plan was activated. No emergency measures were required, neither on-site nor off-site.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Release Pressure (bar)
300.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Flame Type
References
References

Event description in European database eMARS https://emars. jrc. ec. europa. eu/en/eMARS/accident/view/16d71de8-dd2d-8430-0c0f-44b71ad32ac5 (accessed September 2020)

Event description in French database ARIAhttps://www. aria. developpement-durable. gouv. fr/accident/170/ (accessed September 2020)