Explosion in a workshop handling sodium residues
This incident took place at a plant specialised in production of sodium, lithium, and chlorine. A hydrogen explosion occurred during the hydrolysis of sodium residues in a dedicated workshop. During the hydrolysis, the remaining metallic sodium reacted violently with water in an exothermic reaction, releasing hydrogen and causing the explosion. The explosion was audible from outside the site. The smoke and gases released drifted towards the outdoor parking lot, where the sodium deposited and reacted with moisture to form sodium hydroxide. The plant operator marked off the area, shut down the equipment, and performed pH tests. Since the situation stabilised immediately, the plant did not activate its emergency response plan. The incident did not damage the building structure and caused a very light injury.

The INITIATING CAUSE was a reaction between the metallic sodium and water, producing hydrogen. Both the exothermic reaction and the ignition of hydrogen may have contributed to the explosion. The sodium resides, after having been oxidised and before hydrolysis, were usually crushed to guarantee and control a more complete oxidation. In the case of this incident, the crushing had not been performed. The weekend shift staff was reduced, and the procedures allowed for hydrolysis without crushing during weekends. It is unknown if the simplified procedures during the weekend had been established on the basis of a risk assessment or only dictated by the lack of availability of human resources. Anyhow, the ROOT CAUSE can be attributed to shortcoming I the operative procedures, and possibly also in inadequate management decisions.