explosion on a testing unit of rockets

While preparations were being made for a LH2 turbopump test, an explosion occurred above the test cell. Major damage was caused throughout the test facility. A short duration fire caused minor damage. At the time of explosion, a check was being made of the run and catch tank valves. The run tank valve was opened allowing LH2 to enter the run header. The run and return headers were at ambient temperature and the vent valves were closed. LH2 was also being transferred to the gas generator tank which required pressur¬isation of the LH2 run tank. Based on the estimated damage, with blast pressures of 2-3 psig, 10 pounds TNT equivalent was deto¬nated initially and followed by a second detonation equivalent to about 20 pounds TNT. [Ordin, NASA (1974)]

Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The explosion was due to over-pressurization of the bellows assembly in suction duct , followed by activation of a burst disk and subsequent release of about 60 pounds of hydrogen. The IGNITION SOURCE was probably a static charge produced by torn edges of burst disk. Forcing the liquid hydrogen from the run tank into the warm header caused flashing of the liquid and buildup of high pressures sufficient to rupture bellows. The relief valves were not large enough to handle the gases evolved. The bellows failure produced two separate clouds of hydrogen gas joined by a flammable cloud zone which allowed common ignition. A large amount of H2 was considered in the second cloud as being released from the run header.

Facility Information
Application Type
Application
Aerospace
Specific Application Supply Chain Stage
Components Involved

bellow, burst disks, valves and header

Storage/Process Medium
Storage/Process Quantity
55000
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (onsite)

high

Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Mishap no 95 in P. L. Ordin, Review of hydrogen accidents and incidents in NASA operations, 1974, NASA TM X-71565 https://ntrs. nasa. gov/citations/19740020344

Lowesmith et al. , Safety issues of the liquefaction, storage and transportation of liquid hydrogen: An analysis of incidents and HAZIDS, Int. J. Hydrogen energy (2014) https://doi. org/10. 1016/j. ijhydene. 2014. 08. 002

Hankinson and Lowesmith, Qualitative Risk Assessment of Hydrogen Liquefaction, Storage and Transportation, FCH JU project IDEALHY, Deliverable 3. 10 (2013) confidential (accessed October 2025)