Explosion at a silicon coating plant
An explosion and fire occurred at a chemical plant applying silicone coatings. The blast occurred when some polymethyl hydrogen siloxane was accidentally fed into a reactor, together with the correct feedstock, allyl glycidyl ether. The two epoxides reacted, overheated and hydrogen burst out of a ruptured pipe into the building, where it mixed with air and exploded. The 5 workers were caught in the resulting fire. According to the Company, the police believe that human error is to blame. Although both chemicals were labelled, they were stored in drums of the same colour.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
INITIATING cause is the erroneous mixing of a wrong substance (polymethyl hydrogen siloxane) with the correct one (allyl glycidyl ether) in a reactor, causing overheating and hydrogen production. The accidental event occurred in two step: first the rupture of thereactor due to (probably) to overpressurisation from the runaway reaction, secondly the the release, mixing, ignition and explosion of hydrogen in teh building. This could occur because of inadequate chemicals identification so that chemicals were added incorrectly. The ROOT CAUSE could be assigned to shortcoming in procedurea and in management failure in identifying worst case scenarios.