Explosion in a refinery
During the polymerization of ethylene in a 750 litres pressurized reactor, an exothermic runaway decomposition occurred and ethylene and its decomposition products were released through the two reactor vent stacks and via the dump valves on the supply lines. The released gas (cloud) was ignited apparently by the hot carbon particles obtained by the decomposition of the ethylene and an aerial explosion occurred. The following substances were involved in the accident: Ethylene (60 kg). Ethylene (together with the decomposition products about 60 kg). The decomposition products are normally carbon, hydrogen and methane, but no data are available about their amounts. The explosion caused structural damages to the surrounding plants but no data are available about their cost. The released gas was ignited because the automatic water quenching system operated but failed to prevent the aerial ignition. This was due to a quenching system design not appropriate. The intervention of automatic isolation valves on the reactor were not fast enough to prevent more unused ethylene entering the reactor and therefore to feed the aerial explosion. Automatic dump valves on the feeding line operated 2 seconds to dump residual ethylene to atmosphere resulting also in feeding the aerial explosion.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The initiating (process-related) cause was an exothermic runaway decomposition which caused a reactor pressure increase with consequent release of ethylene and its decomposition products. The cause of the ignition of the released gas was probably the hot carbon particles obtained by the decomposition of the ethylene). The automatic water quenching system operated but failed to prevent the aerial ignition. The intervention of automatic isolation valves on the reactor were not fast enough to prevent more unused ethylene entering the reactor and therefore to feed the aerial explosion. The root cause could be attributed to inadequate system design (quenching system and valve opening).