Skip to main content

Explosion in an metallic products plant (746)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion in an metallic products plant

Five barrels of aluminium dust that had been removed from an outdoor dust collector were sealed and stored in the plant adjacent to electrical panels. One of them had somehow been contaminated with water, which exothermically reacted with the aluminium dust to form hydrogen gas. The top of the barrel deformed and glowed red. Smoke was observed and an employee sounded a vocal alarm. The lid blew off the barrel and the mushroom cloud of aluminium dust exploded in a fireball. Nearby combustible material ignited and the sprinkler system activated. The closest employee, sustained second-degree burns of the arm and neck and went to the emergency room for treatment. Due to the warning, there were no other serious injuries.
Event Date
December 2, 1993
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The barrel of aluminium dust outdoor dust collector was contaminated with water and produced hydrogen.
Facility Information
Application Type
Application
Aluminium processing
Specific Application Supply Chain Stage
Components Involved
aluminium powder, dust collector, barrels
Location Type
Operational Condition
Consequences
Number of Injured Persons
1
Number of Fatalities
0
Post-event Summary

Smoke from the barrel was observed and an employee sounded a vocal alarm. Despite the following explosion, only the closest employee was injured, Thanks to the warning, there were no other serious injuries.

Event Nature
Release Type
Release Substance
H2, H2O, Al
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Occupational Safety and Health Administration OHSA Inspection no. 119577575 https://www. osha. gov/pls/imis/establishment. inspection_detail?id=119577575 (accessed November 2020)