Explosion and fire at a university laboratory
The incident occurred at a chemical laboratory of a university. Six students were conducting experiments on producing nitrification carriers for waste leaching when an explosion followed by a fire accident occurred in the laboratory. The cause of the explosion was the accidental production of hydrogen when mixing magnesium powder and phosphoric acid together in a mixer. The hydrogen gas generated in the hopper was ignited by the sparks generated by the metal friction at the rotating shaft of the mixer, which then triggered the explosion of magnesium powder, which ignited the rest of the magnesium fine powder stored in the lab (66 kg) and other combustible materials. Three students were killed. The official investigation concluded several violation of regulations were occurring during university laboratories activities, such as illegal purchase and storage of hazardous chemicals, inadequate safety management. Based on these findings, a legal procedure was started against the project responsible and the laboratory manager. Disciplinary sanctions were decided on university managers covering higher management positions.

The INITIATING CAUSE was the accidental production of hydrogen during the execution of a experiment. The ROOT CAUSE is a sever lack of safety culture, proper risk assessment and preventive and mitigating safety measures throughout the university organisation.