Small explosion in a chemicals manufacturing plant
In a plant producing calcium carbide (CaO + 3C -> CaC2 + CO), a dust collector clogged, probably due to the failure of the cleaning device (nitrogen nozzles) which allowed the dust to build a plug. During the procedure of introducing a poker through an inspection hatch at the lower level, a small explosion occurs and a large amount of dust is ejected through the vent. The cloud containing carbon monoxide and hydrogen ignited. The fire spread to the electrical cables supplying the equipment.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause is the manual intervention executed to free the dust collector. The intervention was inadequate, because executed at the wrong position (under the clogged zone) without the knowledge of the hazards involved (opening of a hatch and mixing hot reactive powders with air). Therefore the root cause is probably related to lack of adequate procedures and/or adequate operative and safety training