Skip to main content

Small explosion in a chemicals manufacturing plant (915)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Small explosion in a chemicals manufacturing plant

In a plant producing calcium carbide (CaO + 3C -> CaC2 + CO), a dust collector clogged, probably due to the failure of the cleaning device (nitrogen nozzles) which allowed the dust to build a plug. During the procedure of introducing a poker through an inspection hatch at the lower level, a small explosion occurs and a large amount of dust is ejected through the vent. The cloud containing carbon monoxide and hydrogen ignited. The fire spread to the electrical cables supplying the equipment.
Event Date
April 9, 1996
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause is the manual intervention executed to free the dust collector. The intervention was inadequate, because executed at the wrong position (under the clogged zone) without the knowledge of the hazards involved (opening of a hatch and mixing hot reactive powders with air). Therefore the root cause is probably related to lack of adequate procedures and/or adequate operative and safety training
Facility Information
Application Type
Application
calcium carbide production (CaC2)
Specific Application Supply Chain Stage
Components Involved
calcium carbide reactor and its components
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
The dust remover of the reactor had clogged and its cleaning required a manual intervention.
Consequences
Number of Injured Persons
1
Number of Fatalities
0
Post-event Summary

According to source, a worker was only slightly injured by incandescent dust jets. The furnace was shut down for 25 hours and the dust collector for 15 days, during which 87 t of dust (lime) was released into the environment. Residents were inconvenienced and traffic on the nearby highway disrupted.

Lessons Learned
The source does not report improvement requirements. Nevertheless, the inadequate manual de-clogging intervention shows that better procedure and better safety training are needed.
Event Nature
Emergency Action
The disaster was controlled in 15 minutes thanks to the intervention of a dozen internalfirefighters.
Release Type
Release Substance
powder and CO+H2 mixture
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description in the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/9944/ (accessed September 2020)