Rupture of a liquid hydrogen line
The pressurisation line on the nozzle skirt of a liquid hydrogen tank ruptured at welded section. Two tests were underway at the same time; one was a pressure test up to 1850 psi (ca. 128 bar) in the gaseous hydrogen circuit and the other was an equipment installation and leak check. The LH2 pressurization line was capped. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The IMMEDIATE CAUSE was the rupture of a pressurised line at a weld. The line ruptured due to high pressure caused by a leakage through a control valve between the gaseous and the liquid systems. The pressure in the pipe reached 1300 to 1400 psi (90 to 97 bar) while its burst pressure was 1250 psi (ca. 86 bar). The ROOT CAUSE of the valve malfunctioning is unknown.