Release from a CGH2 trailer
A pressure relief device (frangible burst disc) on one of a 26 tubes on a tube trailers failed prematurely and released hydrogen while filling a hydrogen storage tank at a government facility. The first responders shut off the supply of hydrogen gas from the tube trailer to the common supply manifold by closing the isolation valve on each of the 26 tubes. The probable pressure value at the moment of the disc opening was 2100 psi (145 bar), while the over-pressure-protection burst disks on each of the tube trailer's 26 tubes had a rated burst pressure of 4000 psi (275 bar). [Source: H2TOOLS]
Event Date
January 16, 2008
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the premature opening of e burst disc. The probable ROOT CAUSE of this event was that the burst disc was degraded by the synergic events of exposure to hydrogen and stress associated with the working pressure involved. A contributing factor in this incident was the burst disc Inconel #600 material that has a high hardness/tensile strength, making it more susceptible to stress corrosion cracking (SCC). It should also be noted that the leak detection step prior to starting the hydrogen fill process is useful for finding leaks in threaded connections, but it could not have detected or predicted the premature failure of the burst disc.