European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre
Jet fire of coke gas in a steel industry (937)
This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.
Jet fire of coke gas in a steel industry
The fire took place during maintenance works in one out of the three gas extractors of the coke process line. Main cause was displacement of a flange which allowed the entrance of flammable mixture gas (methane, carbon monoxide hydrogen and benzene) which ignited probably due to electrostatic spark. According to the ARIA report (see references) total quantity of gas released was 62 400 m³, consisting of 11,7 t CH4, 0,98 t C6H6, 5,1 t CO and 3,4 t H2. During maintenance works, gas extractors were usually isolated and kept under continuous flow of N2. However, in this case, N2 pressure seemed to be not enough to avoid the entrance of flammable gas.
INITIATING cause was probably the inert gas pressure insufficient to prevent the entrance of the flammable mixture.
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.
Contact info
We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.