Hydrogen fire from a piping
The incident occurred at the hydrocracker unit, which was being shut down for maintenance and the reactor was in a hydrogen purge cycle. A hydrogen gas line failed at a weld. The line was at 3000 psi (approx. 200 bar), resulting in a high-pressure hydrogen fire. (1) The fire impinged on the calcium silicate insulation of the skirt of the hydrocracker reactor. (2) The skirt failed causing the fall of the reactor. (3) The falling reactor damaged air coolers and other process equipment, greatly increasing the size of the loss. The initial hydrogen leak is believed to have resulted from the failure of an elbow to reducer weld in the hydrogen preheat exchanger by-pass line.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the failure of a pipe welding. This caused a domino effect with an escalation of the risks and the damages. This suggests a incorrect design risk assessment as ROOT CAUSE. In the course of the evolution of the events, also shortcoming of the management of he emergency procedures became evident.