Hydrogen fire at a chemical plant
The fire broke out in the acid etching tank of the ferric chloride manufacturing unit of a SEVESO-classified chemical plant. In this tank, the attack reaction of the iron metal with hydrochloric acid in solution is carried out, which results in ferrous chloride and hydrogen. The hydrogen generated is swept away by a large supply air fan to maintain the gaseous sky of the tank below the LFL. A few days after the accident, the operator opened and analysed the tank to determine the origin of the fire. According to the ARIA report, the start of the fire was caused by a slow combustion of hydrogen, initiated during the loading of metal. Despite the air circulation, hydrogen accumulated at the bottom of the tank due to its overfilling. The fire then spread outside the tank through the roof opening caused by the degradation of the hydrogen detector and by melting the blast doors. The fire was then alimented by the plastic components of the equipment and the surrounding piping, as well as by the oil from the hydraulic pistons of the roof door of the tank.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause was the overloading of the tank, which allowed accumulation of hydrogen despite the air circulation system. Considering the corrective actions described in the ARIA report, the root cause was probably inadequate safety design and operation.