Hydrogen fire at a chemical plant

The fire broke out in the acid etching tank of the ferric chloride manufacturing unit of a SEVESO-classified chemical plant. In this tank, the attack reaction of the iron metal with hydrochloric acid in solution is carried out, which results in ferrous chloride and hydrogen. The hydrogen generated is swept away by a large supply air fan to maintain the gaseous sky of the tank below the LFL. A few days after the accident, the operator opened and analysed the tank to determine the origin of the fire. According to the ARIA report, the start of the fire was caused by a slow combustion of hydrogen, initiated during the loading of metal. Despite the air circulation, hydrogen accumulated at the bottom of the tank due to its overfilling. The fire then spread outside the tank through the roof opening caused by the degradation of the hydrogen detector and by melting the blast doors. The fire was then alimented by the plastic components of the equipment and the surrounding piping, as well as by the oil from the hydraulic pistons of the roof door of the tank.
Event Date
June 15, 2017
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the overloading of the tank, which allowed accumulation of hydrogen despite the air circulation system. Considering the corrective actions described in the ARIA report, the root cause was probably inadequate safety design and operation.
Facility Information
Application Type
Application
Inorganic chemicals products
Specific Application Supply Chain Stage
Components Involved
reaction tank, production of iron chloride (FeCl2)
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF THE PROCESS The stoichiometric reaction at the basis of the process is: Fe + 2 HCl → FeCl2 + H2
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

No injuries. The unit restarted 6 months after the accident. Damage to the tank upper parts, hydrogen detector and doors

Lessons Learned
The accident suggests that the operative procedure related to the loading of the materials and the preventive measures (hydrogen detection) were inadequate.
Event Nature
Emergency Action
23:40 The Plant safety emergency plan is initiated . 23:53 The fire is reducing 00:50 Despite a small residual still persisting, the fire is extinguished and the reaction unit stopped. 00:45 The emergency plan is called off. 01:25 The leak is sopped.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Flame Type
References