Skip to main content

Fire at a waste liquid storage tank (734)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire at a waste liquid storage tank

When waste alkali solution was taken out of dumper trucks into a waste liquid storage tank, a reaction occurred in the tank. As a result, the solution in the tank foamed over it, and reached an incinerator burning waste wood, when all the waste solution got in flames. The cause of the incident was the waste alkali solution with heavier specific gravity than water, which sank in a mass and came into contact with aluminium powder that had accumulated at the bottom the tank. This resulted in generation of hydrogen gas, which was ignited by fire at the incinerator.
Event Date
June 11, 1996
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the accidental generation of hydrogen gas, ignited by fire at the incinerator. The ROOT CAUSE was identified by the orignal report in: (1) Organization factor (2) Design mistake (3) Prior assessment insufficient.
Facility Information
Application Type
Application
Chemical waste storage and disposal
Specific Application Supply Chain Stage
Components Involved
iquidstorage tank, alkaly tank
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Property Loss (onsite)

21730000

Post-event Summary

21. 73 million yen worth of property damage

Event Nature
Release Type
Release Substance
H2, KOH solution, Al
Hydrogen Release Concentration (%)
0.00
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Orignal source lost. RISCAD is closed.