Fire at a waste liquid storage tank
When waste alkali solution was taken out of dumper trucks into a waste liquid storage tank, a reaction occurred in the tank. As a result, the solution in the tank foamed over it, and reached an incinerator burning waste wood, when all the waste solution got in flames. The cause of the incident was the waste alkali solution with heavier specific gravity than water, which sank in a mass and came into contact with aluminium powder that had accumulated at the bottom the tank. This resulted in generation of hydrogen gas, which was ignited by fire at the incinerator.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments