Fire on a LH2 cryostat
During a cryo-irradiation testing, a Dewar failed or leaked hydrogen into the atmosphere, causing a fire. The Dewar's were nitrogen-walled LH2 vessels to contain metal samples for testing. In the vessel, the hydrogen space was surrounded with vacuum, liquid nitrogen and an external vacuum space. The fire damaged the Dewar with hydrogen gas burning in vicinity of upper part of Dewar. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The hydrogen compartment of the Dewar failed and leak the LH2 into the vacuum space between the liquid hydrogen and the liquid nitrogen. Cooling of the nitrogen compartment which was open to the atmosphere could have resulted in cryo-pumping of air into the vent. The wall between the nitrogen compartment and vacuum space (now filled with liquid hydrogen) failed, allowing air to mix with hydrogen. There were no ignition sources evident. ROOT CAUSE is unknown