Skip to main content

Fire on a LH2 cryostat (327)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire on a LH2 cryostat

This event occurred when dismantling the cryostat. While a hot air dryer was being used to free a coupling in a hydrogen cryostat, a flash fire occurred. [Ordin, NASA (1974)]

Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments

The INITIATING CAUSE the formation of an air-hydrogen explosive mixture in the cryostat. The temperature at the centre of the cryostat was sufficiently low to liquefy air. The ignition of the hydrogen-air mixture was probably due to a spark from an open filament of the dryer. The prescribed requirements for purging and bringing cryostat to room temperature was circumvented. The ROOT CAUSE a human error.

Facility Information
Application Type
Application
Aerospace
Specific Application Supply Chain Stage
Components Involved

cryostat

Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary

The cryostat was being heated up and emptied (probably at the end of an experiment)

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Lessons Learned

In this event, the existing procedure for bringing back the cryostat to room temperature and to dismantle it were not followed. The report does not explain why , but it is easy to assume that the operators wished to accelerate the work and forced a quicker warming up of the coupling by using an heating equipment which clearly was not fitted for the purpose, because not being explosion proof. This suggests a lack of basic knowledge of hydrogen safety principles, and possibly also a lack of supervision or of communication.

Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Mishap no 37 in P. L. Ordin, Review of hydrogen accidents and incidents in NASA operations, 1974, NASA TM X-71565 https://ntrs. nasa. gov/citations/19740020344

Lowesmith et al. , Safety issues of the liquefaction, storage and transportation of liquid hydrogen: An analysis of incidents and HAZIDS, Int. J. Hydrogen energy (2014) https://doi. org/10. 1016/j. ijhydene. 2014. 08. 002

Hankinson and Lowesmith, Qualitative Risk Assessment of Hydrogen Liquefaction, Storage and Transportation, FCH JU project IDEALHY, Deliverable 3. 10 (2013) confidential (accessed October 2025)

Hankinson and Lowesmith, HAZIDs for Hydrogen Liquefaction, Storage and Transportation , FCH JU project IDEALHY, Deliverable 3. 11 (2013) https://www. idealhy. eu/uploads/documents/IDEALHY_D3-10%20HAZIDs_Liquefaction_Storage_Transportation_Summary_web. pdf (Only summary publicly available, accessed October 2025)

Also in H2TOOLS https://h2tools. org/lessons/hydrogen-cryostat-dismantling-incident (Accessed December 2025)