Fire In the hydrodesulphurization unit of a refinery (656)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire In the hydrodesulphurization unit of a refinery

The event occurred at the charge heater (also called a 'fired heater') of a vertical cylindrical hydrodesulphurisation reactor. The heater lost hydrogen flow briefly while the unit was being changed over from recycle to once through hydrogen flow. This operation, performed at start up, aimed at replacing the recycled hydrogen-oil mixture usually used with pure hydrogen. As the hydrogen flow was such a large percentage by volume of the total flow to the exchangers and furnace, the main part of the mass flow at the furnace outlet was lost while the exchangers and heater tubes filled with oil. During this period the outlet tube in one pass overheated and ruptured. The operating procedures did not warn that the furnace fires should be reduced or stopped when making such a changeover. Skin thermocouples were added to the heater outlet tubes at a later date, to monitor local temperature and spot in time temperature run away.
Event Date
January 1, 1970
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was the overheating of a tube of the heat charger, which then failed due to creep. The ROOT CAUSE is related to shortcomings in (1) the operating procedure, which did not prescribe a that the furnace fires had be reduced or stopped when making such a changeover in fluid, and (2) and of the monitoring system, which was not measuring the temperature of individual tubes.

Facility Information
Application Type
Application
Hydrodesulphurisation process
Specific Application Supply Chain Stage
Components Involved
pipe, heat charger, heat exchanger
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF THE UNIT The 'heat charger ' in this incident of 1970 is also called in more recent plant the 'fired heater. In a preparatory step before the fixed bed where the desuphurisation reaction takes place, ". . . the liquid feed is pumped up to the required elevated pressure and is joined by a stream of hydrogen-rich recycle gas. The resulting liquid-gas mixture is preheated by flowing through a heat exchanger. The preheated feed then flows through a fired heater where the feed mixture is totally vaporized and heated to the required elevated temperature before entering the reactor and flowing through a fixed-bed of catalyst where the hydrodesulfurization reaction takes place. " [From the Wikipedia term ‘Hydrodesulfurization’ https://en. wikipedia. org/wiki/Hydrodesulfurization]
Operational Condition
Pre-event Summary

The event happened at stat up, during one-off procedural step condisting in a flow of pure hydrogen in palce of a mixture of oil and hydrogen.

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

Only damage to equipment.

Lessons Learned
This is a case of a material failure in a technical system, due to shortcomings in operating procedure and lack of a monitoring system, able to inform the operator with enough details on deviations from the expected local temperatures. (1) Detailed and effective operating instructions should cover also operations which are performed only one off, or at the start/stop of the operative cycle. (2) Tube skin thermocouples are often used in these systems, because they are the most direct measure of the risk of creep failure on furnace tubes. It is also good practice to provide redundancy, with multiple installation on each tube/pass because skin couples have a tendency to detached from the tubes.
Event Nature
Emergency Action
Probably not required
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description extracted from the UK database ICHEME in PDF ICHEME database is no longer available for purchase, but data can be download as PDF for free. https://www. icheme. org/knowledge/safety-centre/resources/accident-data/ (accessed October 2020)