Fire In the hydrodesulphurization unit of a refinery (656)
This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.
Fire In the hydrodesulphurization unit of a refinery
The event occurred at the charge heater (also called a 'fired heater') of a vertical cylindrical hydrodesulphurisation reactor. The heater lost hydrogen flow briefly while the unit was being changed over from recycle to once through hydrogen flow. This operation, performed at start up, aimed at replacing the recycled hydrogen-oil mixture usually used with pure hydrogen. As the hydrogen flow was such a large percentage by volume of the total flow to the exchangers and furnace, the main part of the mass flow at the furnace outlet was lost while the exchangers and heater tubes filled with oil. During this period the outlet tube in one pass overheated and ruptured. The operating procedures did not warn that the furnace fires should be reduced or stopped when making such a changeover. Skin thermocouples were added to the heater outlet tubes at a later date, to monitor local temperature and spot in time temperature run away.
The INITIATING CAUSE was the overheating of a tube of the heat charger, which then failed due to creep. The ROOT CAUSE is related to shortcomings in (1) the operating procedure, which did not prescribe a that the furnace fires had be reduced or stopped when making such a changeover in fluid, and (2) and of the monitoring system, which was not measuring the temperature of individual tubes.
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.
Contact info
We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.
The INITIATING CAUSE was the overheating of a tube of the heat charger, which then failed due to creep. The ROOT CAUSE is related to shortcomings in (1) the operating procedure, which did not prescribe a that the furnace fires had be reduced or stopped when making such a changeover in fluid, and (2) and of the monitoring system, which was not measuring the temperature of individual tubes.