Fire In the hydrodesulphurization unit of a refinery
The event occurred at the charge heater of a hydrodesulphurisation reactor. The vertical cylindrical fired heater was used on the charge to a hydrodesulphurisation reactor. The flow was two-phase at the heater inlet, consisting in hydrogen and hydrocarbon. At start-up, when the flow was lower than during normal operation, a radiant tube ruptured in one pass. This was thought to be caused by the interruption of the flow in the U tubes of that pass, due to the separation of the liquid-vapour mixture into liquid in the up legs and vapour in the down. Consequently, in absence of flow, the tube overheated and ruptured releasing the fuel, which ignited.
Event Date
January 1, 1971
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the overheating of a tube of the heat exchanger, due to low flow. The ROOT CAUSE is probably related to a shortcoming in the start-up procedure and in the monitoring of the unit critical parameters such as temperature and mass flow. The distribution of flow to the multiple tube passes in this type of installation depends on symmetrical pipework and the pressure drop through the passes. There were no individual pass flow meters. It may have a similar additional root cause components as event no. 656, where the absence of local temperature monitoring prevented the operators to identify deviation from normal operation.