Fire in a hydro-refiner
A tube in a hydrorefiner heater ruptured resulting in an extensive fire inside and outside the furnace. The main fire in the furnace was extinguished within 15 minutes and the escaping gas / vapour release from the ruptured tubes allowed to burn under controlled conditions. There were no injuries to personnel but the furnace suffered damage estimated at £10,000 (1973).
Event Date
January 1, 1974
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The investigations revealed that during changes in operating conditions a cold circulation start-up valve was opened by mistake resulting in liquid feed/hydrogen starvation of the heater tubes for a period of 35 minutes and eventual rupture of the tube with massive release of hydrogen and hydrocarbon vapours.